88 Cards in this Set

  • Front
  • Back
Reactor coolant pump motor amps will ____________ if the rotor is locked and the motor speed will ____________ if the rotor shears. A. increase, increase B. increase, decrease C. decrease, increase D. decrease, decrease
A.
A nuclear power plant is operating normally at 80 percent power when a reactor coolant pump (RCP) shaft seizes. Which one of the following indications would not accompany the seized shaft? A. Reactor coolant system pressure transient. B. Decreased flow rate in the associated reactor coolant loop. C. Decreased flow rate in the remaining reactor coolant loop(s). D. Increased current to the affected RCP with possible breaker trip.
C.
A nuclear power plant is operating at 100 percent power when a reactor coolant pump (RCP) malfunction occurs. Thirty seconds after the malfunction, which one of the following can be used by an operator to determine whether the malfunction is a locked RCP rotor or a sheared RCP rotor? (Assume no operator action is taken.) A. Reactor trip status B. Loop flow indications C. RCP ammeter indications D. Loop differential temperature indications
C.
During a locked reactor coolant pump (RCP) rotor event, RCP current will... A. increase due to the increased rotor torque. B. increase due to the increased stator counter electromotive force (CEMF). C. decrease due to the decreased pump flow. D. decrease due to the increased rotor CEMF.
A.
A nuclear power plant is operating at full power when a reactor coolant pump experiences a locked rotor. How will pump ammeter indication respond? A. Decreases immediately to zero due to breaker trip B. Decreases immediately to no-load motor amps C. Increases immediately to many times running current, then decreases to no-load motor amps D. Increases immediately to many times running current, then decreases to zero upon breaker trip
D.
A cooling water pump is being driven by an ac induction motor. Which one of the following describes how and why pump motor current will change if the pump shaft seizes? A. Decreases due to decreased pump flow B. Decreases due to increased counter electromotive force C. Increases due to decreased pump flow D. Increases due to decreased counter electromotive force
D.
A cooling water pump is being driven by an ac induction motor. Which one of the following describes how and why pump motor current will change if the pump shaft shears? A. Decreases due to decreased pump work. B. Decreases due to decreased counter electromotive force. C. Increases due to increased pump work. D. Increases due to increased counter electromotive force.
A.
A motor-driven centrifugal pump exhibits indications of pump failure while being started in an idle cooling water system. Assuming the pump motor breaker does not trip, which one of the following pairs of indications would be observed if the pump failure is a locked impeller shaft? A. Lower than normal running current with zero system flow rate. B. Lower than normal running current with a fraction of normal system flow rate. C. Excessive duration of peak starting current with zero system flow rate. D. Excessive duration of peak starting current with a fraction of normal system flow rate.
C.
When a motor-driven centrifugal pump is started, the motor ammeter reading immediately increases to, and stabilizes at, many times the normal operating value. Which one of the following describes a possible cause for the ammeter response? A. The pump was started with a fully closed discharge valve. B. The pump was started with a fully open discharge valve. C. The pump shaft seized upon start and did not rotate. D. The pump shaft separated from the motor shaft upon start.
C.
If the generator bearings on a motor-generator begin to overheat from excessive friction, which one of the following will occur next? A. Generator current will begin to increase. B. Generator windings will begin to heat up. C. Motor current will begin to decrease. D. Motor windings will begin to heat up.
D.
A thermal overload device for a large motor protects the motor from... A. sustained overcurrent by opening the motor breaker or motor line contacts. B. sustained overcurrent by opening contacts in the motor windings. C. instantaneous overcurrent by opening the motor breaker or motor line contacts. D. instantaneous overcurrent by opening contacts in the motor windings.
A.
Which one of the following will provide the initial motor protection against electrical damage caused by gradual bearing failure? A. Thermal overload device B. Overcurrent trip relay C. Underfrequency relay D. Undervoltage device
A.
Which one of the following will result from prolonged operation of an ac motor with excessively high stator temperatures? A. Decreased electrical current demand due to reduced counter electromotive force B. Increased electrical current demand due to reduced counter electromotive force C. Decreased electrical resistance to ground due to breakdown of winding insulation D. Increased electrical resistance to ground due to breakdown of winding insulation
C.
Continuous operation of a motor at rated load with a loss of required cooling to the motor windings will eventually result in... A. cavitation of the pumped fluid. B. failure of the motor overcurrent protection devices. C. breakdown of the motor insulation. D. phase current imbalance in the motor and overspeed trip actuation.
C.
Thermal overload devices will provide the first electrical protection for a pump motor in the event of... A. a locked rotor upon starting. B. an electrical short circuit. C. gradual motor bearing damage. D. a sheared shaft during operation.
C.
Which one of the following breaker trip signals will trip the associated motor breaker if a motor bearing seizes while the motor is running? A. Undervoltage B. Underfrequency C. Time-delayed overcurrent D. Instantaneous overcurrent
C.
A main generator that is connected to an infinite power grid has the following initial indications: 100 MW 0 MVAR 2,900 amps 20,000 VAC If main generator excitation is reduced slightly, amps will __________ and MW will ___________. A. increase; decrease B. decrease; decrease C. increase; remain the same D. decrease; remain the same
C.
Excessive current will be drawn by an ac induction motor that is operating... A. completely unloaded. B. at full load. C. with open-circuited stator windings. D. with short-circuited stator windings.
D.
A main generator that is connected to an infinite power grid has the following indications: 500 MW 300 MVAR (out) 2,800 amps If main generator excitation is reduced slightly, amps will __________ and MW will ___________. A. increase; decrease B. increase; remain the same C. decrease; decrease D. decrease; remain the same
D.
A main generator is operating in parallel with an infinite power grid. If the voltage supplied to the generator field is slowly and continuously decreased, the generator will experience high current due to... (Assume no generator protective actuations occur.) A. excessive generator MW. B. excessive generator MVAR out. C. excessive generator MVAR in. D. generator reverse power.
C.
An ac generator is supplying an isolated electrical system with a power factor of 1.0. If generator voltage is held constant while real load (KW) increases, the current supplied by the generator will increase in direct proportion to the ____________ of the change in real load. (Assume the generator power factor remains constant at 1.0.) A. cube B. square C. amount D. square root
C.
A main generator that is connected to an infinite power grid has the following indications: 600 MW 100 MVAR (in) 13,800 amps 25,000 volts If main generator excitation is increased slightly, amps will __________ and MW will ___________. A. decrease; increase B. increase; increase C. decrease; remain the same D. increase; remain the same
C.
A main generator that is connected to an infinite power grid has the following indications: 600 MW 100 MVAR (in) 13,800 amps 25,000 volts If main generator excitation is decreased slightly, amps will __________ and MVAR will ___________. A. decrease; increase B. increase; increase C. decrease; decrease D. increase; decrease
B.
A main generator is connected to an infinite power grid. Which one of the following conditions will exist on the generator if it is operating underexcited? A. Negative MVAR (VARs in) and a leading power factor B. Positive MVAR (VARs out) and a leading power factor C. Positive MVAR (VARs out) and a lagging power factor D. Negative MVAR (VARs in) and a lagging power factor
A.
A diesel generator (D/G) is supplying both KW and KVAR to an electrical bus that is connected to an infinite power grid. Assuming D/G and bus voltage do not change, if the D/G voltage regulator set point is increased slightly, then D/G KW will ________ and D/G amps will ________. A. remain the same; increase B. remain the same; remain the same C. increase; increase D. increase; remain the same
A.
A diesel generator (D/G) is supplying an electrical bus that is connected to an infinite power grid. Assuming D/G terminal voltage and bus frequency do not change, if the D/G governor set point is increased from 60.0 Hz to 60.1 Hz, D/G KVAR load will ________ and D/G amps will ________. A. increase; increase B. increase; remain the same C. remain the same; increase D. remain the same; remain the same
C.
A main generator that is connected to an infinite power grid has the following indications: 600 MW 100 MVAR (out) 13,800 amps 25,000 volts If main generator excitation is decreased, amps will initially __________ and MVAR will initially ___________. A. decrease; increase B. increase; increase C. decrease; decrease D. increase; decrease
C.
A diesel generator (D/G) is supplying both KW and KVAR to an electrical bus that is connected to an infinite power grid. Assuming bus voltage does not change, if the D/G voltage regulator set point is decreased slightly, then D/G KW will ________ and D/G amps will ________. A. remain the same; decrease B. remain the same; remain the same C. decrease; decrease D. decrease; remain the same
A.
A main generator that is connected to an infinite power grid has the following indications: 100 MW 0 MVAR 2,900 amps 20,000 volts If main generator excitation is increased, amps will __________ and MW will ___________. A. remain the same; increase B. increase; increase C. remain the same; remain the same D. increase; remain the same
D.
A main generator is operating in parallel with an infinite power grid. If the voltage supplied to the generator field is slowly and continuously increased, the generator will experience high current due to: (Assume no generator protective actuations occur.) A. generator reverse power. B. excessive generator MW. C. excessive generator MVAR in. D. excessive generator MVAR out.
D.
Two identical 1,000 MW electrical generators are operating in parallel supplying the same isolated electrical bus. The generator output breakers provide identical protection for the generators. Generator A and B output indications are as follows: Generator A Generator B 22 KV 22 KV 60.2 Hertz 60.2 Hertz 800 MW 800 MW 50 MVAR (out) 25 MVAR (in) A malfunction causes the voltage regulator for generator B to slowly and continuously increase the terminal voltage for generator B. If no operator action is taken, generator B output current will... A. increase continuously until the output breaker for generator A trips on overcurrent. B. increase continuously until the output breaker for generator B trips on overcurrent. C. initially decrease, and then increase until the output breaker for generator A trips on overcurrent. D. initially decrease, and then increase until the output breaker for generator B trips on overcurrent.
D.
A cooling water system is being returned to service following maintenance on the two identical centrifugal cooling water pumps. The two pumps (see figure below) take suction from a common suction header and discharge to a common discharge header. Each pump is driven by a three-phase ac induction motor. Pump A was started five minutes ago to initiate flow in the cooling water system. Pump B is about to be started. When pump B is started, which one of the following would cause the ammeter for pump B to remain off-scale high for several seconds longer than usual before returning to normal running current indication? A. The pump packing was removed and not reinstalled. B. The pump was initially rotating in the reverse direction. C. Two phases of the motor windings were electrically switched. D. The coupling between the motor and the pump was removed and not reinstalled.
B.
A main turbine-generator is operating in parallel with an infinite power grid. If the turbine control valves (or throttle valves) slowly fail open, the generator will experience high current primarily due to... (Assume no generator protective actuations occur.) A. excessive generator MW. B. excessive generator VARs out. C. excessive generator VARs in. D. generator reverse power.
A.
A main generator is operating and connected to an infinite power grid. Elevated main generator winding temperature requires a reduction in reactive load from 200 MVAR (out) to 150 MVAR (out). To accomplish the reactive load reduction, the operator must ____________ the generator field current; when generator reactive load equals 150 MVAR (out) the generator power factor will be ___________than the initial power factor. A. increase; larger B. increase; smaller C. decrease; larger D. decrease; smaller
C.
A main generator is operating and connected to an infinite power grid with the following initial generator parameters: Terminal Voltage: 22 KV Frequency: 60 Hertz Load--Real: 575 MW Load--Reactive: 100 MVAR (in) Power Factor: 0.985 Which one of the following contains a combination of manual adjustments to the main generator voltage regulator and speed control setpoints such that each adjustment will initially result in an increase in main generator amps? Voltage Speed Setpoint Setpoint A. Increase Increase B. Increase Decrease C. Decrease Increase D. Decrease Decrease
C.
A nuclear power plant startup is in progress. The main generator has just been connected to the power grid with the following generator indications: 10 MW 0 MVAR 288 amps 20,000 volts The operator suspects that the main generator is operating under reverse power conditions and attempts to increase generator load (MW) normally. If the main generator is operating under reverse power conditions when the operator attempts to increase generator load, generator MW will initially ____________; and generator amps will initially ____________. A. decrease; decrease B. decrease; increase C. increase; decrease D. increase; increase
A.
A main generator is operating and is connected to an infinite power grid with the following initial generator parameters: Terminal Voltage: 22 KV Frequency: 60 Hertz Load--Real: 575 MW Load--Reactive: 100 MVAR (in) Power Factor: 0.985 Which one of the following contains a combination of manual adjustments to the main generator voltage regulator and speed control setpoints such that each adjustment will initially result in a decrease in main generator amps? Voltage Speed Setpoint Setpoint A. Increase Increase B. Increase Decrease C. Decrease Increase D. Decrease Decrease
B.
A main generator is connected to an infinite power grid with the following initial generator parameters: Voltage: 22 KV Frequency: 60 Hertz Load--Real: 600 MW Load--Reactive: 100 MVAR (out) Power Factor: 0.986 Which one of the following contains a combination of manual adjustments to the main generator voltage regulator and speed control setpoints such that each adjustment will initially result in an increase in main generator amps? Voltage Speed Setpoint Setpoint A. Increase Increase B. Increase Decrease C. Decrease Increase D. Decrease Decrease
A.
A main generator is connected to an infinite power grid. Which one of the following pairs of main generator output parameters places the generator in the closest proximity to slipping a pole. A. 800 MW; 200 MVAR (in) B. 800 MW; 600 MVAR (in) C. 400 MW; 200 MVAR (out) D. 400 MW; 600 MVAR (out)
B.
A main generator is connected to an infinite power grid with the following initial generator parameters: Voltage: 22 KV Frequency: 60 Hertz Load--Real: 600 MW Load--Reactive: 100 MVAR (out) Power Factor: 0.986 Which one of the following contains a combination of manual adjustments to the main generator voltage regulator and speed control setpoints such that each adjustment will initially result in a decrease in main generator amps? Voltage Speed Setpoint Setpoint A. Increase Increase B. Increase Decrease C. Decrease Increase D. Decrease Decrease
D.
During a surveillance test, a 4,000 KW diesel generator and a 1,000 MW turbine generator at a nuclear power plant are connected to a power grid. The following stable generator conditions exist: Diesel Generator Turbine Generator 700 KW 800 MW 200 KVAR (out) 100 MVAR (out) A malfunction then occurs, causing the voltage regulator for the turbine generator to slowly and continuously increase the generator field excitation current. If no operator action is taken, the diesel generator output current will __________ until the turbine generator output breaker trips. A. remain about the same B. increase continuously C. initially increase, and then decrease D. initially decrease, and then increase
D.
A main generator is operating normally and connected to an infinite power grid with the following initial generator parameters: Terminal Voltage: 22 KV Frequency: 60 Hertz Load--Real: 575 MW Load--Reactive: 100 MVAR (in) Power Factor: 0.985 Which one of the following contains a combination of normal adjustments to the main generator voltage regulator and speed control setpoints such that each adjustment will cause the main generator to operate at a power factor closer to 1.0. (Assume that generator power factor remains less than 1.0.) Voltage Speed Setpoint Setpoint A. Increase Increase B. Increase Decrease C. Decrease Increase D. Decrease Decrease
A.
If the speed of a variable speed centrifugal pump is increased to cause pump flow rate to double, pump motor current will... A. remain constant. B. increase two-fold (double). C. increase four-fold. D. increase eight-fold.
D.
A centrifugal pump is operating with the following parameters: Pump speed = 1,800 rpm Pump head = 100 psid Motor current = 10 amps What will be the new value of pump head if the speed is increased such that the current requirements are now 640 amps? A. 400 psid B. 800 psid C. 1,200 psid D. 1,600 psid
D.
A centrifugal pump has a flow rate of 3,000 gpm and a current requirement of 200 amps. If the pump speed is reduced such that the flow rate is 2,000 gpm, what is the final current requirement at the new lower speed? (Assume a constant motor voltage.) A. 59 amps B. 89 amps C. 133 amps D. 150 amps
A.
A centrifugal pump is operating with the following parameters: Speed = 1,800 rpm Current = 40 amps Pump head = 20 psi Pump flow rate = 400 gpm Which one of the following will be the new value of pump head and current if the speed is increased to 2,000 rpm? A. 22 psi, 49 amps B. 22 psi, 55 amps C. 25 psi, 49 amps D. 25 psi, 55 amps
D.
A centrifugal pump is operating at 600 rpm with the following parameters: Current = 10 amps Pump head = 50 psi Pump flow rate = 200 gpm What will be the new value of pump head if the flow is increased such that the current requirements are now 640 amps? A. 400 psi B. 600 psi C. 800 psi D. 1,200 psi
C.
A motor-driven centrifugal pump is operating at a low flow condition in an open system. The throttled discharge valve is then fully opened to increase system flow rate. Which one of the following will increase? A. Pump discharge pressure B. Available net positive suction head C. Motor amps D. Pump speed
C.
A centrifugal pump is operating with the following parameters: Speed = 3,600 rpm Current = 100 amps Pump head = 50 psi Pump flow rate = 400 gpm What will be the new value of pump head and current if the speed is decreased to 2,000 rpm? A. 8.6 psi, 30.1 amps B. 8.6 psi, 17.1 amps C. 15.4 psi, 30.1 amps D. 15.4 psi, 17.1 amps
D.
A two-speed centrifugal pump is driven by an ac motor with the following initial conditions: Pump speed = 400 rpm Motor current = 40 amps Pump head = 60 psid If pump speed is increased to 1600 rpm what will be the new pump head? A. 240 psid B. 480 psid C. 960 psid D 3,840 psid
C.
A centrifugal pump is operating with the following parameters: Speed = 1,200 rpm Current = 40 amps Pump head = 20 psi Pump flow rate = 400 gpm What will be the approximate value of pump head and current if pump speed is increased to 1,600 rpm? A. 25 psi, 55 amps B. 25 psi, 95 amps C. 36 psi, 55 amps D. 36 psi, 95 amps
D.
A centrifugal pump is operating with the following parameters: Speed = 1,200 rpm Current = 40 amps Pump head = 20 psi Pump flow rate = 400 gpm What will be the approximate value of pump head and current if pump speed is increased to 1,800 rpm? A. 36 psi, 95 amps B. 36 psi, 135 amps C. 45 psi, 95 amps D. 45 psi, 135 amps
D.
A centrifugal pump is operating with the following parameters: Speed = 1,800 rpm Current = 40 amps Pump head = 20 psi Pump flow rate = 400 gpm What will be the approximate value of pump head and current if pump speed is decreased to 1,200 rpm? A. 13 psi, 18 amps B. 13 psi, 12 amps C. 9 psi, 18 amps D. 9 psi, 12 amps
D.
An ac motor-driven centrifugal pump is operating with a flow rate of 3,000 gpm and a motor current of 150 amps. If the pump speed is reduced such that the flow rate is 2,000 gpm, what is the approximate final motor current at the new lower speed? (Assume a constant motor voltage.) A. 44 amps B. 59 amps C. 67 amps D. 100 amps
A.
A centrifugal pump is operating at 600 rpm with the following parameters: Motor current = 100 amps Pump head = 50 psid Pump flow rate = 880 gpm Which one of the following will be the approximate value of pump head if pump speed is increased to 1,200 rpm? A. 71 psid B. 126 psid C. 172 psid D. 200 psid
D.
A multi-speed centrifugal pump is operating at 3,600 rpm with a flow rate of 3,000 gpm. Which one of the following approximates the new flow rate if the speed is decreased to 3,000 rpm? A. 1,000 gpm B. 1,500 gpm C. 2,000 gpm D. 2,500 gpm
D.
A multispeed centrifugal pump is operating with a flow rate of 1,800 gpm at a speed of 3,600 rpm. Which one of the following approximates the new flow rate if the pump speed is decreased to 2,400 rpm? A. 900 gpm B. 1,050 gpm C. 1,200 gpm D. 1,350 gpm
C.
A multi-speed motor-driven centrifugal pump is operating with the following parameters: Motor current = 27 amps Pump head = 50 psi Pump flow rate = 880 gpm Which one of the following will be the approximate new value of pump head if pump speed is increased such that the motor current is now 64 amps? A. 89 psi B. 119 psi C. 211 psi D. 281 psi
A.
Which one of the following describes the relationship between the current supplied to an ac induction motor and the amount of heat generated in the motor windings? A. Heat generation is directly proportional to the current. B. Heat generation is proportional to the cube of the current. C. Heat generation is proportional to the square of the current. D. Heat generation is proportional to the square root of the current.
C.
A centrifugal pump is operating at 600 rpm with the following parameters: Current = 100 amps Pump head = 50 psid Pump flow rate = 880 gpm What will be the approximate value of pump head if pump speed is increased such that the pump now draws 640 amps? A. 93 psid B. 126 psid C. 173 psid D. 320 psid
C.
A rotary positive displacement pump (PDP) is being used to supply water to a piping system. The PDP is driven by an ac induction motor. The initial parameters are: System pressure: 500 psig PDP flow rate: 50 gpm PDP motor current: 40 amps After several hours, the PDP motor speed is increased such that the new PDP flow rate is 100 gpm. If system pressure does not change, what is the approximate value of the PDP motor current at the 100 gpm flow rate? A. 80 amps B. 160 amps C. 320 amps D. 640 amps
A.
Refer to the pump performance curves for a centrifugal cooling water pump (see figure below). The pump is being driven by a single-speed ac induction motor. Pump flow rate is being controlled by a throttled discharge flow control valve. The following initial pump conditions exist: Pump motor current: 50 amps Pump flow rate: 400 gpm If the flow control valve is repositioned such that pump flow rate is now 800 gpm, what will be the approximate new pump motor current? A. Less than 100 amps B. 200 amps C. 400 amps D. More than 500 amps
A.
Consider two identical single-speed ac induction motors, one of which is connected to a radial-flow centrifugal pump and the other to a reciprocating-type positive displacement pump (PDP). Both pumps are taking suction at the same elevation from a vented water storage tank. Each pump has a maximum design backpressure of 800 psig, and each is operating with the following initial conditions: Flow rate: 200 gpm Backpressure: 400 psig Motor current: 100 amps If the backpressure for each pump increases to 600 psig, the centrifugal pump will have a ___________ flow rate than the PDP; and the centrifugal pump will have a ___________ motor current than the PDP. A. lower; higher B. lower; lower C. higher; higher D. higher; lower
B.
Refer to the pump performance curves for a centrifugal cooling water pump (see figure below). The pump is being driven by a single-speed ac induction motor. Pump flow rate is being controlled by a throttled discharge flow control valve. The following initial pump conditions exist: Pump motor current: 100 amps Pump flow rate: 800 gpm If the flow control valve is repositioned such that pump flow rate decreases to 400 gpm, what will be the approximate new pump motor current? A. Less than 15 amps B. 25 amps C. 50 amps D. Greater than 75 amps
D.
A 4,160 VAC three-phase induction motor is connected to a radial-flow centrifugal pump in a cooling water system. When the pump is started, the time period required to reach a stable running current will be shorter if the pump discharge valve is fully _______; and the stable running current will be lower if the pump discharge valve is fully _______. A. open; open B. open; closed C. closed; open D. closed; closed
D.
The starting current in a typical ac induction motor is typically much higher than the full-load running current because... A. starting torque is lower than full-load running torque. B. starting torque is higher than full-load running torque. C. rotor speed during start is too low to generate significant counter electromotive force in the stator. D. rotor current during start is too low to generate significant counter electromotive force in the stator.
C.
The average starting current for an ac motor is approximately... A. the same as its normal running current. B. two to three times its normal running current. C. five to seven times its normal running current. D. ten to fifteen times its normal running current.
C.
Which one of the following describes the motor current indications that would be observed during the start of a large ac motor connected to a load? A. Amps slowly increase to the normal operating value over a period of five time constants. B. Amps immediately increase to the normal operating value and stabilize. C. Amps immediately increase to many times the normal operating value and then decrease to the normal operating value. D. Amps immediately increase to the full-scale value and then decrease rapidly to zero due to overload protection.
C.
If the discharge valve of a large motor-driven centrifugal pump is kept closed during a normal pump start, the amps indication for the ac induction motor will rise to... A. several times the full-load current value and then decrease to the no-load current value. B. approximately the full-load current value and then decrease to the no-load current value. C. several times the full-load current value and then decrease to the full-load value. D. approximately the full-load current value and then stabilize at the full-load current value.
A.
Which one of the following is a characteristic of a typical ac induction motor that causes starting current to be greater than running current? A. The rotor field induces an opposing voltage in the stator that is proportional to rotor speed. B. After the motor starts, resistors are added to the electrical circuit to limit the running current. C. A large amount of starting current is required to initially establish the rotating magnetic field. D. The rotor does not develop maximum induced current flow until it has achieved synchronous speed.
A.
The starting current in an ac motor is significantly higher than the full-load running current because... A. little counter electromotive force is induced onto the rotor during motor start. B. motor torque production is highest during motor start. C. little counter electromotive force is induced onto the stator during motor start. D. work performed by the motor is highest during motor start.
C.
Starting current in an ac induction motor is typically ____________ times full-load rated current. A. 1/4 to 1/2 B. 2 to 3 C. 5 to 6 D. 10 to 12
C.
Which one of the following describes the motor current during the start of a typical ac motor-driven radial-flow centrifugal pump with a closed discharge valve? (Assume the pump does not trip.) A. Current immediately increases to the full-load value and then gradually decreases to the no-load value. B. Current immediately increases to the full-load value and then stabilizes at the full-load value. C. Current immediately increases to many times the full-load value and then rapidly decreases to the no-load value after several seconds and then stabilizes. D. Current immediately increases to many times the full-load value and then rapidly decreases to the full-load value after several seconds and then stabilizes.
C.
Which one of the following describes the motor current indications that would be observed during the start of a large ac motor-driven radial-flow centrifugal pump with a closed discharge valve? A. Current immediately increases to the full-load value and then gradually decreases to the no-load value over several minutes. B. Current immediately increases to the no-load value and then stabilizes. C. Current immediately increases to many times the no-load value and then rapidly decreases to the no-load value after several seconds. D. Current immediately increases to many times the no-load value and then gradually decreases to the no-load value after several minutes.
C.
Two identical 4,160 VAC induction motors are connected to identical radial-flow centrifugal pumps being used to provide cooling water flow in separate systems in a nuclear power plant. Each motor is rated at 1,000 hp. The discharge valve for pump A is fully open and the discharge valve for pump B is fully shut. If each motor is then started, the longest time period required to stabilize motor current will be experienced by motor ___________ and the higher stable motor current will be experienced by motor ________. A. A; A B. A; B C. B; A D. B; B
A.
Which one of the following describes when the highest stator current will be experienced by an ac induction motor? A. During motor operation at full load B. During motor operation at zero load C. Immediately after energizing the motor D. Immediately after deenergizing the motor
C.
Two identical 4,160 VAC induction motors are connected to identical radial-flow centrifugal pumps in identical but separate cooling water systems. Each motor is rated at 200 hp. The discharge valve for pump A is fully shut and the discharge valve for pump B is fully open. If each motor is then started, the longer time period required to stabilize motor current will be experienced by motor ___________ and the higher stable motor current will be experienced by motor ________. A. A; A B. A; B C. B; A D. B; B
D.
Two identical 4,160 VAC three-phase induction motors are connected to identical radial-flow centrifugal pumps in identical but separate cooling water systems. Each motor is rated at 200 hp. The discharge valve for pump A is fully shut and the discharge valve for pump B is fully open. When the motors are started under these conditions, the shorter time period required to reach a stable running current will be experienced by motor ___________, and the higher stable running current will be experienced by motor ________. A. A; A B. A; B C. B; A D. B; B
B.
Select the option that correctly fills in the blanks. To minimize the adverse effects of starting current, an ac induction motor should be started ____________ to ___________ the stator counter electromotive force (CEMF). A. unloaded; quickly establish B. unloaded; delay C. partially loaded; quickly establish D. partially loaded; delay
A.
Two identical 4,160 VAC three-phase induction motors are connected to identical radial-flow centrifugal pumps in identical but separate cooling water systems. Each motor is rated at 200 hp. The discharge valve for motor/pump A is fully open and the discharge valve for motor/pump B is fully closed. When the motors are started under these conditions, the shorter time period required to reach a stable running current will be experienced by motor ___________, and the higher stable running current will be experienced by motor ________. A. A; A B. A; B C. B; A D. B; B
C.
What is the primary reason for limiting the number of starts for an electric motor in a given period of time? A. Prevent overheating of the windings due to high starting currents. B. Prevent overheating of the windings due to shorting within the stator. C. Prevent rotor damage due to excessive cyclic stresses on the shaft. D. Prevent rotor damage due to excessive axial displacement of the shaft.
A.
Which one of the following is the basis for restricting the number of starts that a large ac motor may be subjected to within a one-hour period? A. Prevent excessive torsional stresses on the motor shaft B. Prevent excessive arcing and degradation of motor breaker contacts C. Prevent excessive heat buildup within the motor windings D. Prevent excessive wear of motor thrust bearings
C.
The number of starts for an electric motor in a given period of time should be limited because overheating of the ______________ can occur due to the ______________ counter electromotive force produced at low rotor speeds. A. windings; low B. windings; high C. commutator and/or slip rings; low D. commutator and/or slip rings; high
A.
The frequency of start/stop cycles for an electrical motor is limited to prevent... A. overheating the motor windings. B. overheating the motor supply bus. C. excessive shaft torsional stresses. D. excessive cycling of the motor breaker.
A.
Frequent start/stop cycling of large ac motors is prohibited to prevent... A. excessive bearing wear. B. motor shaft imbalance. C. overloading electrical buswork. D. overheating motor windings.
D.
Frequent starts of large motors will result in overheating of the motor windings due to high current flow caused by... A. low electrical resistance of the motor windings. B. an electrical short circuit between the rotor and stator. C. high counter electromotive force at low rotor speeds. D. windage losses between the rotor and stator.
A.
Which one of the following is the primary reason for limiting the number of motor starts in a given time period? A. Minimizes pitting of contacts in the motor breaker. B. Prevents excessive torsional stresses on motor shaft. C. Prevents overheating of motor windings. D. Minimizes axial stresses on motor bearings.
C.
A large centrifugal pump is driven by a 200 horsepower 4.16 KV ac motor. The motor breaker control circuit contains the following protection devices: instantaneous overcurrent relay, motor thermal overload relay, control power fuses, and an anti-pumping device. The pump had been manually started and stopped several times during a 5-minute period when the motor breaker unexpectedly tripped. In this situation, which one of the following is the most likely cause of the breaker trip? A. Instantaneous overcurrent B. Motor thermal overload C. Blown control power fuse D. Anti-pumping device actuation
B.