• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
Front

How to study your flashcards.

Right/Left arrow keys: Navigate between flashcards.right arrow keyleft arrow key

Up/Down arrow keys: Flip the card between the front and back.down keyup key

H key: Show hint (3rd side).h key

image

PLAY BUTTON

image

PLAY BUTTON

image

Progress

1/4

Click to flip

4 Cards in this Set

  • Front
  • Back
List the parameters used by the SGWLC Program to generate a signal in the Feedwater Pump Speed Control System.
Feed Header Pressure, Steam Header Pressure, Total Steam Flow, and No-load setpoint.
What parameters are the Main Feedwater Pump Speed Control System programmed to maintain a differential pressure between?
Steam Header and Main Feedwater Header.
During normal operation at power, what would a sudden steam flow/feed flow mismatch on one steam generator most likely be an indication of?
A failure of a single Main Feedwater Regulating Valve controller.
During normal operation at power, what would a sudden steam flow/feed flow mismatch on all steam generators most likely be an indication of?
A load rejection or a MFP Master Controller failure.