Shipping used refrigerant
|
To much **** to type |
|
Ozone in stratosphere consists of molecules containing |
3 oxygen atoms |
|
Unlike other chlorine compounds and naturally occurring chlorine,the chlorine in cfcs and hcfcs will ? |
Neither dissolve in water nor break down into compounds that dissolve in water |
|
HFCs are made up of hydrogen, fluorine and carbon. They do NOT contain? |
Chlorine that effects the ozone layer but most HFCs have a high GWP |
|
Most HFC refrigerants such as R-410A |
Have global warming potentials thousands of times greater then carbon dioxide |
|
The global warming potential of isobutane (R600a) propane (R-290) and R441a are significantly lower |
When compared to GWP of HFCs such as (R-134a,R-407c,R-404a and R-410a |
|
Azeotropic refrigerants mixtures contains 2 or more refrigerants.at a certain pressure an azeotropic mixture evaporates and condenses at constant temperature |
It acts like a single component refrigerant over its entire range |
|
Zeotropic or non azeotropic refrigerants their blend may be ? |
Maybe binary (2 parts ) or ternary (3 parts) |
|
Temperature glide can range ? |
A few tenths of a degree to 12degrees or more |
|
The R 400 series of refrigerants are near azeotropic blends that can leak from a system at uneven rates due to? |
Different vapor pressure which can effect the percentage of each refrigerant remaking in the system |
|
The EPA does not approve any substitute refrigerant as direct drop in replacement to service any? |
R22 or any other system |
|
Most HCFC binary and ternary blends use |
Alkylbenze lubricant |
|
Care must be taken when using ester based oils ? |
They are very hydroscopic and will absorb moisture out of the air and through some containers |
|
The clean air acts (epa regulations) allows for releasing refrigerant ? |
A small amount of refrigerant mixed with nitrogen (trace gas) for leak detection |
|
Reclamied refrigerant must meet ? |
AHRI standard 700 |
|
Technicians can only charge used CFC HCFC or HFC if |
Appliance is owned by same customer |
|
Recovery equipment must be tested according to |
AHRI standard 740 |
|
Recovery devices remove refrigerant from a appliance without assistance from other components |
Self contained |
|
Recovery devices remove refrigerant from a appliance without assistance from other components |
Self contained |
|
Recovery that relies on the compressor in the appliance is ? |
System dependent |
|
Epa requires appliances that do not have service valves to have ? |
Aperture or process’s stub |
|
Release of CFC,HFC HCFC or HFO refrigerant is ? |
Prohibited |
|
A technician must have separate refrigerant cylinders for |
Each type of refrigerant and should have a separate cylinder for know mixed refrigerant |
|
Most manufacturers require system evacuation to ? |
500 microns or lower |
|
When pressurizing a system with nitrogen you should always charge through |
Pressure regulator and a relief valve in the downstream line from the pressure regulator |