Sentronic oil control: red switch to the left means it's ____

tripped

Sentronic oil control: Check for voltage between terminals __ and ___

L and M

What is a turba-shred?

A type of Emerson oil separator, which collects oil droplets on the compressor discharge and returns the oil from its reservoir along a high pressure line to the oil pressure differential regulator valve .This valve reduces the oil pressure to between 20 and 25 psig above the crankcase pressure of the compressor, providing even flow of oil to the oil level regulators or floats.

What should be added to a residential or commercial system after an acid burnout?

Add flare burnout filter drier on both lines, also add injectable acid neutralizer

Is it a good idea to add a filter drier to the suction line?

No, this kills the compressor

What do older compressors have for sensors?

Cap tubes. They can leak due to vibration, and can be replaced with encapsulated switches and transducers

Hill Phoenix door heaters use fuses. T/f

True

What should 404a be replaced with? Is it a straight drop in?

R448a, aka Honeywell n40 solstice. "Near" drop in

On a defrost timer, what are terminals 3 and 4

3 is the defrost heater, 4 is the refrigeration circuit

Max filling of recovery cylinder?

80% of volume

How to measure condenser approach

Temp difference between condenser water leaving temp and condenser liquid line temp (carrier says 0-3 degrees F)

How to measure discharge setpoint and discharge air temp with eng a DJM

Setpoint: VDC , PT 1 and PT3, multiply by 10



Volts DC, PT1 and PT (not labelled), multiply by 10

How to jumper heat to Eng A DJM board:

Jumper across FS and HS

How to troubleshoot eng a DJM ignition failure

Ensure flame relay is pulled in, should have 24 volts across FR and neutral

Autoflame login

hold start and commission until menu changes.



Enter password 25401



What is condenser split?

Outside air temp subtracted from condensing temperature.




i.e: 125 F condensing temp - 95 F ambient = 30 F split

How to pull a vacuum

Jb eliminator,


blue hose to suction and ball valve, supco gauge between blue hose and red hose going to vacuum pump

Would a condenser approach of 9 be too high or too low?

Too high

How is condenser approach calculated

Should be 0-3 degrees. Difference between liquid line temp and leaving condenser water temp

What refrigerant can 407c be a retrofit refrigerant for

r22

What is r449 a retrofit gas for?

404a, 507, 407a/f and r22

Atb bms login

https://www.ubiquitysystems.net/UB4/index.php?SPAGE=/UB4/1_1.php&QSTR=SITEID=10078



UsernameEPotterPasswordGateway2!


Honeywell economizer enthalpy curve we use

Curve D

20 mesh strainer on evap Inlets. 20 mesh is very small. 60 mesh is small

Quantech

Motor shafts measured 1/8"

Driven shaft measured in 1/16th

Cpr: CCW to Lower amps




CCW to reduce suction pressure in crankcase



CCWTo increase suction pressure in evap


CW to increase amps



CW to increase suction pressure in crankcase



CW to reduce suction pressure in evap

Save on login:

Jdiaczun


6055

Test microthermo sensor temp wires by shorting them and by opening them

Should be -50 or 150, can't remember which is which. I think 150 is open wire

TCS sensors communication problems rsading:

90 F for open


40 F for a short

Bitzer compressors

Brandon Houston There is no pump, so no screen. Its a slinger so oil is slung around and collected in a cup on the end of the crank. It’s an optic safety that looks for oil in the cup.



Have you pulled and cleaned the optic eye? It "sees" the oil by detecting the millivolt signal created by the oil itself. Sometimes the eye itself gets dirty and has issues with rectifying



Brian Harju some do have a screen behind the drain plug, it fooled me once !! Never again!!



Micro thermo SLA

Safety line alarm. safety line alarm. Any time a safety is tripped, with MT, the system reads it as a generic SLA. Whether it’s low pressure, high pressure, oil, etc....



we have had a problem with the compressor module setting it off randomly. No safety’s are tripping.

Isolating compressors:

Always valve off the suction or the crankcase will get flooded with oil (as per mike Harding.

Holdback valves

Never overtighten the auto/manual switch - it's just a needle valve and it will leak.



Never overtighten the bolts that bolt the actuator to the valve. (As per Mike Harding)

Expansion tank location in piping

Not on discharge side of pump. Somewhere upstream on the suction

How to fix leaking valve stem

Turn valve all the way in before tightening the packing nut.

Traulsen coolers evap frozen up

Replace temp sensor

Lochinvar setup menu

Shutdown in the menu.



Once in shutdown mode, press and hold select button. Password 5309

Loss of charge on trane CGAM - bad suction thermistor or suction transducer

bad suction thermistor or suction transducer



The loss of charge diagnostic is generated when the ratio of EXV % Flow Command/Superheat Control Compressor Flow Estimate is 1.7 or greater.The ratio should be 1 to 1. Everyone I've come across was due too a bad suction line temperature sensor. The EXV % Flow Command/Superheat Control Compressor Flow Estimate can be trended when adding/subtracting charge. As the line come together the charge is good. Know this due to a contractor seeing this diagnostic and dumping 30 extra pounds of gas into the machine (had a bad temp sensor).

Trane cgam exv

Little sightglass with white ring moves when manually overriding txv

Trane passwords

159 or 314

Thermotek HMI password

1234

Traulsen unlock

Hit middle button twice

Traulsen settings

555

On Carrier chillers if the model starts with 30 it has either a scroll, screw, or reciprocating compressor and the first letter determines the compressor type. Most of the time they have multiple compressors and are under 500 tons. If the model number starts with 19 like a 19XR it is a centrifugal. If the model number starts with 23 like a 23XR it is a water cooled screw machine with a single compressor. The third letter let's you know if the machine has a VFD. If the third letter after the first two numbers is a V than the compressors are on VFDs.

Carriee

An RTAC500 is an air cooled screw chiller. The third letter in the model of every Trane chiller refers to the type of condenser (RTAA is an air cooled screw chiller The A let's you know that an RTHC is a water cooled screw machine the H stands for hydrogen AKA water) the last later is the model in that series and the first two letters tell you the compressor type. RT stands for Rotary Trane AKA Trane's name for their screw compressors just like the CV in a CVHE stands for Centravac Trane's name for their centrifugal compressors. And yes just one of those compressors is almost 50k not including the labor to replace it. Those compressors weigh about 1600lbs. I work for Daikin and one of our 500 ton screw compressors weigh almost 2500lbs.

Trane

Walmart

15% markup parts


90 regular rate


130 overtime


50 bucks


On CO2, Medium temp compressors are



Low temp compressors are

Transcritical compressors



Subcritical

Kes misting bad pump

Pipe water bypassed from RO filters into misting solenoid. And then bypass pump piping

E2 alarm bypassing

Input definitions, bypass: yes, set time for 12 hrs, at 0deg, see ya tomorrow!

Hold back valve in -45 c with rack down

Set to manual let it buck for 10 minutes, and that will get the rack going while you go get refrigerant

E2 access

Hit Alt F for FULL access

Epr : in to increase sst, out to lower. Cw is in, ccw is out

. Cw is in, ccw is out

E2 multiple cases on a circuit

Instead of having the temp set at MAX in the setup, change it to MIN. Fort sask walmart/curtis

Co2 transcritical and subcritical:

Subcritical: below 88 f



Transcritical: above 88 f



Triple point: -70 f



Hillphoenix antisweatt heaters

Check for sweatmiser in electrical room, one relay controls one case. Bypass the relay

Oil screen plugged sysmptoms

If oil pressure starts strong and then gradually drops until OFC cuts out

Save on foods calgary trail code

23298#

WIF Freezer fans not coming on

Check door switch

Cant find small leaks?

Check compressor wire nut connections. Refrigerant can travel through the wire insulation. Especially on encapsulated pressure control wirings

Uncommon places to leak check

Motor and compressors erpeckerheads

Microthermo node test fail

Check little orange wiring harness in the back of the computer for a tight connection

Purolator number gateway

6059099

Eng A mtrac system problem

Just saying that heat switch is open

Compressor proof failure

Check oil pressure in reservoir, should be 20 psi differential above suction pressure. If differential is too low check oil filter pressure drop. If there is a pressure drop, replace oil filter

Siemens, jci, and others use 20 pounds

Honeywell 18 psi

Time delay relays

Replace with Eaton TRL04, they never fail

Set holdback valve for 70 f condensing sct

70 f

Bypass valve set for 65 F sct

Set fans for 80 f sct

sporlan a8 and a9

a8 is holdback valve - open of rise of inlet
a9 is a "hot gas bypass valve" - close on rise of outlet (maintains pressure in receiver when a8 is holding back)



leave gas ballast open until hitting ___ microns

2500

what is dead heading vacuum pump?

putting vacuum gauge directly onto vacuum pump and seeing how low pump can go

what component do you need with an ORI for condenser flooding?

an ORD or CRO

How to check check valve for bleed by on a case?

Close SDR or EPR and watch case suction temp. It should stay the same. If it keeps rising to liquid temp, its passing.



It will also frost on inlet of check valve if flowing backwards.



Floodback is also a symptom.



Maybe infrared gun

High temp alarm on a case, previously the night before. How to diagnose?

Check the rack head pressure /condensing pressure graphs and logs at the time of the high temp alarm. If head pressure was low at the time, could be low on refrigerant. Check receiver.

In MT, under Networks, there is an option to test all the nodes. Takes 25 min according to derek. To avoid nuisance errors,

Find the equipment in MT and uncheck "test node periodically"

Ecojkmizer, test discharge air sensor by hampering t1 and t2, should open up dampers wide

.

Co2 critical point

88 f sat, or 1055 psi.Above this temp it is transcritical

Sporlan EEV troubleshooting

Multimeter to AC, when valve is driving, Black and white, and red and green, 12 volts between each pair

Micro Thermo eev

Base value needs readjusting: average of a normal good case should base value

Arctic chiller login

user: USER


Pass: user

Trane cgam temp sensor

Not holding water or refrigerant back, just threads into a. Thermowell

Chiller inverted start

When the condenser is colder than the evap. Causes problems for motor and drive cooling

Approach

"usually" your approach temp should not be higher than whatever your temp difference between in and out is.


Replacement for 134a

513a

How to know if oil separator is plugged

If line coming out of the bottom is cold

Tower water in on bottom, out on top

Chiller water in on top, out on the bottom