ACCESO A ASCENSOR DE EMERGENCIA |
DESDE ESCALERA PROTEGIDA O VESTIBULO INDEPENDIENTE DE ESCALERA ESPECIALMENTE PROTEGIDA, PUERTA E30 DESDE RECINTO DE ESCALERA ESPECIALMENTE PROTEGIDA, NO SERA NECESARIO E30 |
|
CAPACIDAD DE CARGA ASCENSOR DE EMERGENCIA |
630 KG (minimo) |
|
DIMENSIONES DE CABINA ASCENSOR DE EMERGENCIA |
1,10 x 1,40 m |
|
DIMENSIONES DE CABINA DE ASCENSOR EMERGENCIA USO HOSPITALARIO |
1,20 x 2,10 m |
|
ASCENSOR DE EMERGENCIA DEBE PERMITIR RECORRIDO COMPLETO |
MENOS DE 60´´ |
|
CUANDO SE ACCIONA BOTON "USO EXLUSIVO DE BOMBEROS" DE ASCENSOR DE EMERGENCIA |
ENVIA EL ASCENSOR A LA PLANTA DE ACCESO Y SOLO MANEJO DESDE LA CABINA |
|
EN CASO DE FALLO DE ABASTECIMIENTO DE ASCENSOR DE EMERGENCIA |
FUENTE PROPIA QUE DISPONDRA DE AUTONOMIA DE 1H, MINIMO |
|
MAXIMA ALTURA SALVADA DE RECORRIDO DE EVACUACION. HASTA UNA SALIDA DE PLANTA |
GENERAL = 4 m HOSPITAL ( TRATAMIENTO INTENSIVO ) = 1 m DOCENTE ( INFANTIL-PRIMARIA ) = 1 m |
|
MAXIMA ALTURA A SALVAR DE RECORRIDO DE EVACUACION. HASTA EL ESPACIO EXTERIOR SEGURO |
GENERAL = 6m HOSPITAL ( TRATAMIENTO INTENSIVO ) = 2 m DOCENTE ( INFANTIL-PRIMARIA ) = 2 m |
|
CURVA NORMALIZADA TEMPERATURA. UNE EN 1363:2000 |
15´= 740ºC 30´= 840ºC 45´= 900ºC 60´= 950ºC 90´= 1000ºC 120´= 1050ºC 180´= 1100ºC 240´= 1150ºC |
|
VALOR CARACTERISTICO DE DENSIDAD DE CARGA DE FUEGO |
COMERCIAL = 730 MJ/m2 RV = 650 M7/m2 H-RP = 280 MJ/m2 ADM = 520 MJ/m2 D = 350 MJ/m2 PC = 365 MJ/m2 A = 280 MJ/m2 |