• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/70

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

70 Cards in this Set

  • Front
  • Back

Shut off valves for backflow prevention SB

Resilient seated shut off & full flow characteristics


- Full port Ball valves


- Resilient wedged gate valves



Bypass arrangement, Jumper connections,


removable sections swivel or change over


devices, hoses and hose bibs or the presence of an abundance of piping that cannot be traces.


Are examples of ?

A Potential Cross-Connection sitiuatioin

***


Physical location of CC protection devices


(plateforms for the testable devices)


Measured from Centerline Heigh above floor:


PVB / SPPVB No more then ____


SCVAF / DCVA / DCVAF _____


RP / RPF

PVB / SPPVB No more then 5 ' (1500mm)


SCVAF / DCVA / DCVAF 2 1/2 - 5' &750-1500)


RP / RPF 2 1/2 - 5' &750-1500)

AG, AVB, PVB, DCVA These protect against?

BACKFLOW MODERATE CONDITION

AVB , DCAP protect in what applications

BACKFLOW MINOR

LFVB Application,


Lab Faucet Vacuum Breaker

-Protect against Back siphonage only

- NOT to be used under constant pressure conditions


- Used to isolate MINOR hazards




* Used for Moderate, Severe hazards area or Premise isolation

Provision for Electrical currents on back flow


protection devices

If a backblow prevention assembly is to be


removed from the line.


Provide a jumper wire to by-pass strong electrical currents

Test cocks need to be what type

SB Resilient seated test cocks w full flow charteristics:


ball valves


plug valves


port needle valves

Generally speaking 3 authorities which concern themselves directly/individually with the quality & safety of water as it relates to health they are:

Perveyor or the Water Utility


Plumbing Inspector


Medical Officer of Health

Where should an approved Backflow protection assembly be installed?

Installed at the Service Connection to any


premises where there is an auxiliary water supply even though there is not connection or cross connection.

Backflow - Severe Hazard what is used


* Backflow not necessarly back pressure

AVP


PVB


RP


AG


* Backflow not necessarly back pressure



DUC / DCV


how to know the difference

DUC, Duel Check vavle non testable


DCV, Double Check valve, Testable

Barometric Loop, is it good CC protection?


(Using the principle that a perfect vacuum can only lift water approx 10.4m or 34ft. A loop rising 107m or 35ft above the highest fixture on the premise being served. SB inspected yearly)

Not recommended, backflow protection because: - Cumbersome


- Difficult to protect from freezing


- Can be easily nulified through tie-ins or bypass arrangements

AG, Air Gap what size

- Unobstructed vertical distance between the


lowest opening from any pipe/fauchet conveying


water or waste to a tank, fixture AND the Flood Level Rim (FLR) of the receptable.


- 2 x Pipe D or 1"


- Never less than 1"




What is Back Siphonage

- Reversal of the normal direction of flow, due to Negative Pressure (Vacuum) being created in the system.


- This reduction in pressure causes atmospheric pressure to force polluted water up through a submerged fixture inlet.

Where would an Air Gap not be installed

- An Approved Air Gap SNotB installed in an


environment where the atmosphere maybe


contaminated i.e Fumehood


- For this reason Air Gaps SB included in yearly inspections.

What is a Severe Hazard Level

A Cross Connection (or potential) involving any substance iin sufficient concentration to cause death, spread disease or illness

What is a Minor Hazard condition

Existing condition, or potential connection


between the domestic water pipe and any pipe, vat or tank intended for holding potable water which has a low probability of becoming a


Moderate Hazard.

How do repairs contribute to Cross-Connection

Whenever a distribution system is shutdown to accomidate repairs, a negative or reduced


pressures will occur at all locations within the


affected system which lie at the hight elevation then the break.

Back Pressure

A pressure higher then the supply pressure


- Booster pump w/o backflow protection


- Potable water connections to boilers / other pressure devices w/o prevention devices


- Interconnection with other system operated at a higher pressure i.e. fertilzer injection system


- Water main break or Pumping for a Fire

An Atmosheric vacuum breaker,


Dual check valve


Hose connection VB


Dual check valve with Atmospheric ports are:

Non Testable devices

Are Plumbing Permits required to install Cross Connectio devices

-Yes, permits are required to install RP's, Double Check valves and Pressure Vacuum breakers


- No premits reqired for testing/repairing


*These are testable devices and must be


registered upon installation*

Area Protection

Protection provided for a piping system section with potable and non-potable connections


downstream of a back flow preventer

Can strainers be used on RP's used for Fire Protection

- No, strainers SNotB used in Fire supression


system as they reduce the flow characteristics


- ULC could approve but must inquire.

Can a RP be by-passed?

- 24 hrs of uninterrupted service a by-pass or


parallel arrangement SB installed.


- By pass must have the same degree of backflow protection.

What is an Auxiliary Water Supply

Any water supply source or system other than the public water supply, that maybe available in a building or on a premise.

What is a Moderate Hazard

A cross connection (or potential) involving any substance which has a low probability of


becoming a severe hazard and would constitute a nuisance.

What is a Critical Level

Level of submergence at which the back siphonage preventer ceases to prevent Back siphonage.

RP is constantly leaking

To a point it is doing its Job however


- Either the 1st check valve, the 2nd check valve or the Relief valve has failed.


The check valves SB cleaned of possible debris & rubber seat checked for damage

***


Where must an AIR Gap be used

Air Gaps must be used


- Sewage equipment


- Non-potable or auxiliary water systems


- Any lethal substance

Potential toxicity or probabiltiy of back flow what is of more concern?

The Rick factor due to potential toxicity is of greater concern when selecting a backflow


preventor than probability of backflow

What can happen with a pump as they pertain to back siphonage

Back siphonage is the result of reduced water system pressure on the suction side of an in-line booster pump

What is a Backflow Preventer

An assembly or device which prohibits the


backflow of water into the potable water supply


* If it is open to atmosphere SNotB located where it could contaminate the water supply & the opening to atmoshere could be submerged & spillage from opening undersirable.

AVB Installation requirements

- No operation > the 12 hours continous pressure


- Installed min of 6" above FLR


- Vertically & where spillage is not objectionable


- Effective against Backflow Only

***


PVB Installation requirements

- Installed min of 12" above FLR


- Vertically & where spillage is not objectionable


- Effective against Backflow Only

***


Inplant or Premise isolation, what is better

Wherever possible, provide inplant isolation


(fixture and/or zone) because inplant personnel are protected and in most cases the back flow preventer can be siged smaller due to smaller


inplant piping.

Can pumps pose a contamination issue

Considerable case must be exercised to prevent the use of the suction side line to pumps for


sanitary, laboratory or industrial uses on lower floors.


Polutants or contaminants from equipment


supplied by take-off from the suction side line may easily be pumped through out the upper floors

What is Backflow & What causes backflow

- Flowing back/reversal of the normal direction of flow, allowing waste to enter a building through the drainage system.


- Causes: Unusual heavy rains, overloaded public sewers (undersize) blocked public sewers

Anti-siphon breaker


(Device containing a shut-off valve followed by a valve body containing disc float assembly, a check seat and an air inlet port allowing water


to drain)

- A device installed on a line that is designed to prevent a vacuum from forming in a piping system.


- Device can be under continous pressure.


* Don't confuse with a Atmospheric vacuum breaker.

Area-Isolation

- Confinement of sources of pollution or


contamination, existing/potential, within a


specified area


- Each source of pollution or containment within the controlled area maybe required protection.



Centreline Height above floor?


(platforms for the testable devices

Any installation with a > centreline measurement shall be proveded witha fixed Platform under assembly


PVB/ SPPVB no more than 5' (< 1500mm)


SCVAF/DCVA/ DCVAF 2.5-5' (750-1500mm)


RP / RPF 2.5-5f (750-1500 mm)



How long does a customer have to fix a failed device

Testable cross connection control device repaired or replaced & retested within 5 working days.

RF opening pressures

Relief valve shall open at a minimum pressure differential of 13.8 kpa or an RP back flow preventer or 6.9 kPa for a RPF backflow preventer, as measured across check valve 1

What needs to happen if a failed device if found

An approved tester must submit a report in writing to the Director of Water Resources on as approve form within 2 business days where not repaired.

RPF ?


Parts ?

Same components as a RP & is designed specifically for use in Fire Protectiopn systems.


The min relief valve opening point is 6.9 kPa (1psi)


* RP opening point is 13.8 kPa or 2 psi

What is the minimum check valve differential of a DCVAF?

Minimum check valve differential of a DCVAF is


3.4 kPa or 0.5 psi

Shut off #2 close and RP leaking

If shut off valve #2 on a RP is closed water begins to discharge from the relief valve port, check valve #1 is probably leaking. The check valve should be cleaned if possible debris & rubber seat checked for damage.

HCDVB flow function position of valves in normal flow pressure limitations

- No flow through the device the check valves are closed and the vent is open


- Designed for pressure only on water demand for short intermittent periods of time.

What si the minimum check valve differential of a DCVA?

Min check valve differential of a DCVA is 6.9 kPa (1psi)

Shut off assemblies install after Jan 1, 1987, with metal to metal shut off valve or test cocks will be considered Unapproved

Unapproved

HCVB Host connection Vacuum Breaker

Force loaded check valve biased to NC position and an atmospheric vent that is NO Normally Open.

HCDVB Hose connection duel check Vacuum breaker

Consits of 2 independently acting check valves, force loaded to NC position.


Between the 2 checks is a means of venting to atmoshere force loaded to NO position

How many hours is a testin course?


What mark do I need to on the exam


- Testers course of instruction shall be 30 hours


- Need a mark of 75% on the exam

Protection required for single story clinic


Multi Story Clinic

- Single-story clinic, a double check valve will be adequate in most cases


- A reduced Pressure princble assembly for hospitals, mortuary, morque autopsy or any multi-storied clinic

Alarm Check what is it and is it an approved back flow preventer ?

A single, soft seated check valve which may or may not be internally loaded will sound an alarm when the check valve opens.


Shall have suitable connections for testing the water tightness & operation


* NON Approved backflow Preventer

What should happen if both shutoffs are closed & test cock #2 is open

I both shutoffs are closed & test cock #2 is open, water should begin to discharge from the relief valve port

LFVB Installation:


Back siphon / Back pressure?


location

Shall not be installed in a vent hood or wherre toxic / objectionable fumes occur.


- Installed on the Discharge side of the last control valve.


- Installed on a typical lab faucet goose neck.

Is a permit required for a DUC?


Dual check valve assembly

No, not a testable device

Tester Recertificaiton requirements?

Tester recertifationcause 9 hours min 3 hours ot Theory


Min of 6 hours of practical


75 % on written exam


Satifactory completion of practical exam

HCDVB test pressure & time?

When back pressure equivalent to 3m of Heat is applied DS checkvalve on a HCDVB device, it shall not leak for 6 seconds or more this is normal


> 6 seconds however indicates the atmospheric vent if faulty and that the HCDVB device should be repaired.

LFVB Laboratory Faucet Vacuum Breaker

2 independently acting check valves, force loaded or biased to a normally closed position, and between the check valves there is a means of automatically venting to atmosphere that is forced loaded or biased to a NO position.

LFVB Function:


Normal flow, no flow

Normal flow, primary check valve opens & the atmosheric vent is closed off by the deflection of a diaphram seal. The second check valve opens permitting flow throught the device.


- No flow (under pressure but not flow)


Primary check valves seats against the diaphram which in turn seals the atmosheric vent & the secondary check valve closes.

LFVB Function Back siphonage

When back siphonagfe occurse the secondary check valve closes & the primay check valve seals / c;pses agaomst the diaphram.


The atmospheric vent is open permitting air to enter.


In the event that the secondary check valve fails, leakage would be vented through the atmospheric vent.`

RP Installation

- RP installed readily accessible


- Protectedfrom freezng & > from 43C (110F)


- Not be installed in a Pit/ or below ground level


- Relief valve port must have approved AB or max Flood Level (greater of two)


- If not for Fire Protection, a strainer ahead of preventer insome localities.


Horizontal Position


No Corrosive Fumes

SCVAF Function & Installation

Normal operation, the check valve opens permitting flow - Upon Backflow the check would close highly,preventing contamination of supply.


Install: readily accessible with adequate space


- No Pits unless drainage provided


On test cocks removed & plugged


- Horizontal Positioin

1-SCVAF single check valve assembly for Fire Systems


2- Application?

One internally loaded check valve installed between 2 tightly clising, resilient seated, shut off valves, complete with test cocks


2- Designed for use in Fire Protection systems that are constructed of acceptable potable water system materials, and that would only consitute a MINOR hazard

What happens when RP supply pressure drops?

If the supply pressure drops, the relieve valve will maintain a minimum pressure in the zone between the 1st and 2nd check valves of approximently 13.8 kPa (2psi) & Lower that the supply pressure by releasing suffienient water to maintain the required differance in pressure. If supply pressure becomesa < 2 psi & the relief valve opens & discharges the reduced pressure zone the atmosphere



HCDVB / HCVB Installation

- Installed on hose threaded outlets i.e hose bibs, service sinks and wall hydrants


- installed on the discharge side of control vlve


- so air vent are not submerged


- not be subject to continous pressure


- Drainage type & it > 43C or above HW type required


- no toxit fumes


- where spillage is not objectionable

RP doesn't open after by passing water from High side to low side, what could be there reason

The Differential pressure relief valv doesn't open after by -passing water from hight to low side this could indicate either the relief valv e is falulty or shout off 2 is leaking


- If it the relief valve pressure will drip to 0Kpa


- If the shut off valve #2 the lower guage will need to be opened more than 1/4 open.

HCVB Function:


normal


backsiphonage

Normal flow the force leaded check valve opens and the atmospheric vent closes allowing water to flow thought the device


- No flow or with Back siphonage occurs the foruce leaded check valve will close, opening the atmospheric vent, allowing aire in the downstream.