EXCEPTUADOS DE COMPARTIMENTACION INTERIOR

RV, ADM, D Y RP = NO>500 m2

TIENEN SECTOR DE INCENDIO

PUBLICA CONCURRENCIA = O > 500P


ZONA APARCAMIENTO = SC > 100m2

RESIDENCIAL VIVIENDA

SC DEL SECTOR DE INCENDIO = NO > 2500 m2


ELEMENTOS QUE SEPAREN VIVIENDAS = Al menos EI60

COMERCIAL

SC DEL SECTOR DE INCENDIO = NO > 2500 m2

ESTABLECIMIENTOS O CENTROS QUE OCUPEN INTEGRAMENTE UN EDIFICIO

UN UNICO SECTOR DE INCENDIO CUANDO


AE [descendente] NO > 10 m


AE [ascendente] > 4 m

CENTROS COMERCIALES DE PUBLICA CONCURRENCIA

AL MENOS UN SI = SC > 500m2

DOCENTE [1 SOLA PLANTA]

NO NECESARIO SI

DOCENTE [ MAS DE 1 PLANTA ]

SC DEL SI NO > 4000 m2

PUBLICA CONCURRENCIA Y RESIDENCIAL PUBLICO

SC DEL SI NO > 2500 m2

APARCAMIENTO

SI CUANDO ESTE INTEGRADO EN EDIFICIO CON OTROS USOS.

APARCAMIENTO ROBOTIZADO

SITUADO DEBAJO DE OTRO SI NO > 10000 m2

HOSPITALES [ PLANTAS CON UNIDADES ESPECIALES ]

2 SI = SC NO > 1500 m2

OTRAS ZONAS DE HOSPITALES

SC DEL SI NO > 2500 m2

AMPLIACION SECTORES DE INCENDIO

PUEDEN DUPLICARSE CUANDO ESTEN PROTEGIDAS CON INSTALACION AUTOMATICA DE EXTINCION

RESISTENCIA AL FUEGO DE PAREDES, TECHOS... QUE DELIMITAN SI. BAJO RASANTE

RV, RP, D, ADM = EI 120



C, PC, H = EI 120 ( EI 18O = AE + 28 )



A = EI 120 ( EI 180 = APARCAMIENTO ROBOTIZADO )

RESISTENCIA A FUEGO DE PAREDES, TECHOS... QUE DELIMITAN SI. PLANTA SOBRE RASANTE

RIESGO MINIMO CUALQUIER USO = EI 120



RV, RP, D, ADM = AE - 15 ( EI 60 ) AE 15-28 ( EI 90 ) AE + 28 ( EI 120 )



C, PC, H = AE - 15 ( EI 90 ) AE 15-28 ( EI 120 ) AE + 28 ( EI 180 )



A = EI 120

LOCALES EN ZONAS DE RIESGO ESPECIAL INTEGRADOS EN EDIFICIO

RESISTENCIA FUEGO DE ESTRUCTURA PORTANTE


RB ( R90 ) RM ( R120 ) RA ( R180 )



RESISTENCIA FUEGO DE PAREDES Y TECHOS QUE SEPARAN ZONAS


RB ( EI 90 ) RM ( EI 120 ) RA ( EI 180 )



MAXIMO RECORRIDO HASTA ALGUNA SALIDA LOCAL = MAX 25 m