23 Cards in this Set
- Front
- Back
Three sides of fire triangle |
Oxygen, Fuel, Ignition |
|
____ is produced when materials _______ react to form simpler compounds. |
Heat, Exothermically |
|
What type of detector is suited for a atrium location. |
Projected beam detector |
|
Pyrolysis |
Burning fuel produces smoke without flames |
|
What kind of detector is most appropriate for an elevator lobby in an apartment building? |
Spot-type smoke detector |
|
NFPA 90A, HVAC systems that deliver over ____ CHM generally _______ shutdown and _______ side smoke detection during a fire alarm situation. |
2000, fan, supply |
|
Name an example of smoke control |
Stair pressurization |
|
1 indicates a single tap, 111-11111-11-1 from street box generates what box # at public fire dispatch center? |
3521 |
|
Street boxes transmit their coded number how many times minimum? |
3 |
|
The first fire reporting system was installed in ____? |
Boston, 1852 |
|
A central station must have a min of ? Operators on duty at all times and a min of ? Means of re-transmission. |
2, 2 |
|
______ alarm supervising stations only monitor owned accounts? |
Proprietary |
|
The primary means of communication for a DACT must be a (n) _______? |
Loop start telephone line |
|
A DACT requires a minimum of ____ means of communication between the protected premises and the fire alarm sup. Station. |
2 |
|
A DACT may take up to ____ seconds per dialing attempt. |
90 |
|
The primary purpose of dwelling fire warning equipment is ____? |
Life safety |
|
Multiple-station smoke alarms for dwelling use cannot be ____ between individual dwelling units. |
Interconnected |
|
The national institute of Standards & Technology conducted test on smoke alarms in _____ in the 1970s |
Indiana Dunes |
|
Heat detectors installed in an attic with a maximum ambient temp of 120º F must be designed & rated to operate at a min of _____º F. |
145 |
|
Smoke detectors installed within _____ feet of a cooktop or range must be of the _____ type. |
21', photoelectric |
|
Dwelling smoke alarms must produce an audible _____ signal for at least _____ minutes. |
Evacuation, 4 min |
|
Rechargeable power supplies for smoke alarms must recharge in ____ hours or less when connected to a ____ portion of branch circuit. |
4, switched |
|
Who is the responsible party to ensure that the fire alarm is properly inspected, tested, and maintained? |
The owner |