Forced air system heating heat the space from where to where?

From the ceiling down

Baseboard heating Heats through?

Convection

Fin baseboard is made of three components?

Copper tube aluminum fins and enclosure

Radiant Heating Heats what

Surrounding surfaces

Advantages of radiant floor heating over conventional forced air?

Lower temperature stratusfaction, minimal air movement


and higher surface temperatures of objects in the room.

How is the response time for radiant floor heating?

Slow

Radiant floor heating systems don't allow for?

Air filtering, purification or humidification. Systems must be installed to maintain air quality.

Applications for radiant Heating?

Residential, commercial, industrial, snow melt, Agriculture and sports field applications.

Three categories of tubing for radiant floor heating?

Metallic, synthetic and composite.

The ability of oxygen molecules to pass through a material?

Oxygen permeation.

Composite tubing consists of?

PE/AL/PE


A thin layer of aluminum sandwiched between two layers of plastic.

Recommended length for 3/8" copper?

250'

Recommended length for 1/2 inch copper?

300'

Recommended length for three quarter inch copper?

500'

The rule of thumb recommended flow rate for residential?

2 to 4 feet per second

Recommended floor temperature four areas where people stand?

77 °f

Recommended floor temperature in dwelling or commercial spaces?

88°f

Recommended floor temperature in bathrooms, swimming pools, and for foyers?

91 °f

Balancing valves are not required if there is less than what percent difference between the longest and shortest circuit?

10%

With heat loss calculations you must round up to the nearest?

.25 / quarter inch of a foot

DTD is the difference between?

Your IDT and your ODT

Transmission loss?

Conduction through a material

For heat loss calculations what percent must be added for bathrooms?

20%

R value is?

The resistance to flow. IE- window. Wall. Or combination of products.

What requires you to know the pressure drop through a system, gallons per minute required and temperature drop through the circuit?

Pump sizing

Where is the lowest pressure point in a pump and in radiant floor heating systems?

At the inlet of the pump

Where is the best location for a pump?

At the point of no pressure change.

What is required in order to properly size a boiler for an application?

Total heat load required for the building

What recommendations should be followed when installing boilers?

Manufacturer's recommendation

What type of boiler is best suited to Supply heating water directly to an in floor heating system?

Condensing boiler

How many BTUs in one pound of water

970 BTUs

Conventional boilers must operate at what temperature?

Above 140°F

Condensing boilers operate at what temperature?

Below 140 °F

What is the greatest advantage of hydronic heating over any other system?

Multiple zoning

Which one of the following floor coverings has the greatest R-value?


A) hardwood B) ceramic tile C) vinyl tile D) carpet and underlay

C) vinyl tile

What three factors must you know in order to size tubing?

Gallons per minute flow rate,


length of the circuit and


design temperature drop through the circuit.

A typical velocity in a residential application is between?

2 and 4 feet per second.

In a piping layout how much temperature drop is there across a circuit?

15 to 20 degrees across the circuit

Good practice is to install tubing along an exterior wall at what spacing?

6"

The counter flow pattern is used when heat loss is?

Evenly distributed

Tubing should be fastened every?

3 feet and on arches

What three factors must be known in order to properly size tubing for an application?

GPM, velocity and length of circuit

What is the required minimum measurement when a pressure test is on for a radiant floor heating system?

The greater of either 60 PSI or 1.5 x working pressure for 1 hour

What two factors are required to calculate header size?

GPM and velocity

What is required when piping a low mass boiler that is flow sensitive?

A bypass pump between the supply and return boiler piping

What is required when a conventional boiler is installed in a low temperature radiant floor heating application?

A mixing valve

What is the first step in servicing a boiler venting and Main burner?

Turn off the electrical and gas supplies

What is the best way to clean a main burner?

Vacuum and soft brush

What type of thermostat is used on a hot water heating system?

A thermostat without a heat anticipator.

A loose wire on an aquastat may?

Prevent to the main Berner from firing.

What will happen to a non-condensing boiler when the return water temperature is too low?

There will be unnecessary damage and boiler failure.

What is the code for hydronic heating systems?

B 214