Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
46 Cards in this Set
- Front
- Back
what is the mag sprink pub?
|
S9522-AA-HBK-010
|
|
what is the HSD FUSIBLE LINK temperature?
|
161 +/- 1
|
|
what is the other name for F ALARM?
|
ICJ 105
|
|
what is the transmission tubing lines made of?
|
ROCKHIDE
|
|
what is the minimum loop between vented check valves and prpv?
|
4"
|
|
what is the purpose of the loop between vented check valves and prpv?
|
shock mounting
|
|
can transmission line be sectionally replaced if punctured?
yes or no and why? |
no because it must be SEAMLESS
|
|
what is the max amount of copper tubing that can be exposed?
|
1"
|
|
how much of the copper tubing must be covered by rock?
|
1/8"
|
|
is it ok to paint the rockhide covering?
|
no becuse it adds extra insulation that can compromise the heat sensing ability plus it's flammable
|
|
what type of fitting goes on the transmission tubing ends?
|
37° flare fitting
|
|
what's the maximum hsd's per prpv?
|
12
|
|
what's the max OSI per PRP?
|
not to exceed 24 OSI
|
|
what's an R4Q?
|
it's the quarterly pms flush
|
|
what OSI do you pump the mag sprink to for a flush?
|
16-20 OSI then allow to settle
|
|
what's the minimum LOOP for flex hoses?
|
10" (wire mesh tubing)
|
|
what's an 81M
|
spring loaded lift check valve
|
|
what's the purpose of a spring loaded lift check valve?
|
to prevent backflow
|
|
what's HORCV stand for?
|
hydraulically operated remote control valve
|
|
What's the purpose of HORCV |
allows system to be secured from a station other than the one that actuated it |
|
what's CM15
|
most common type of 3way manual control valve
|
|
what happens to drain line during open loop?
|
steady flow through drain line one
|
|
what happens to drain lines during a closed loop?
|
steady flow from drain line two and a gush of water from #3 which turns into a diminished flow
|
|
what is an orifice plate made of?
|
MONEL (70% copper and 30% nickel)
|
|
what size hole is in an orifice plate?
|
.098" diamater hole OR #40 drill bit
|
|
how do you order an orifice plate?
|
ask the machine shop.. they make them. hence the reason we say #40 drill bit
|
|
how do you clean copper tubing of the mag sprink?
|
with a brass brush and water only (not hot sauce!!)
|
|
what type of system is the mag sprink?
|
dry type
|
|
what's another name for MSV?
|
CLA-VALVE
|
|
what's the operating PSI of the MSV?
|
40 PSI
|
|
whats the operating PSI of a navy standard msv?
|
55 PSI
|
|
where should the FD alarm be located?
|
1.5 to 2 inches from deck
|
|
At what temperature does the F alarm light off at? |
105° +/- 1 |
|
which do you shut off first, local or remote??
|
the one that's in OPEN goes to NEUTRAL FIRST
|
|
what's the purpose of PORT BRAVO?
|
check for leaking of diaphram
|
|
what's purpose of PORT CHARLIE?
|
troubleshoot air pressure trapped in POWERTROL
|
|
another name for PORT CHARLIE
|
CHATTERING VALVE
|
|
what does it mean if there's a leak at port DELTA? |
o-ring retainer (around stem) is fucked |
|
what's purpose of PORT ALPHA?
|
inlet of water
|
|
What max area do HSD's protect? |
120 sqft |
|
how many hsd's are required per space?
|
2 min
|
|
hsd's must be installed within how many feet of a BOUNDARY BULKHEAD?
|
8
|
|
hsd's shall not be loacted within how many feet of ventilation?
|
5
|
|
can you put hsd's above or below cooling coils?
|
NO
|
|
how far from bulkheads and i beams minimum distance for placement of HSD'S
|
at least 1 foot away
|
|
max length of transmission tubing?
|
50 ft
|