64 Cards in this Set

  • Front
  • Back

how much do you reduce corrugated liner?

20%

how much must high altitude appliances must be derated?

10%

how much do you reduce each elbow in a vent?

10%

when a draft hooded appliance has more than two 90° elbows on a vent connector, how much should it be de rated?

10%

when a fan assisted appliance on a vent connector has more than two 90° elbows, how much should it be de rated?

15%

if you were to reduce a fan assisted appliance from 4" to 3" .... how much do you reduce from the vent sizing tables?

10%

the minimum size of a vent or vent connector?

equal to 3" in diameter

minimum size of a vent or chimney if it's not round?

2"

what is the size of the vent connector serving a single appliance?

same size as the draft hood

what is the size of a common vent connector serving a single appliance with multiple draft hood outlets?

the combined area of all the outlets

what is the minimum size of a chimney serving a single appliance?

one size larger than the vent connector

what is the formula to size a vent serving multiple appliances?

100% of the area of the largest output +50% of the rest

what is the minimum size (area) of a chimney?

12 in² (77cm²)

what is the maximum size of a masonry chimney for a given installation?

not to exceed the appliances input by more than 25%

what is the minimum height of an air supply inlet above ground?

6"

what is the minimum size of an opening screen, Louvre, or grille used for air supply?

1/4"

what is the maximum developed length of an air supply duct allowed without increasing in size?

20'

what is the minimum area for a square or rectangular duct used for air supply?

9 in²

what type of damper is allowed for installations on an air supply duct in a dwelling unit?

a certified automatic damper

where should an air supply duct terminate?

next to the burner of the largest appliance

what is the minimum size of a fresh air intake and duct?

4"

what two types of buildings are there?

-loose construction


-air tight

what type of building is loose construction?

type B

what type of building is air tight construction?

type A

all houses, old or new, are considered to be _______ unless told otherwise

classed as air tight

where must air supply openings and ducts be located?

1 ft above burner level


2 ft horizontally

what would be declared if a zero is entered into the tables of a loose building?

no outdoor air supply is needed

what appliance does ROT only apply for?

Category 1 Natural Draft Hood

when do you not use ROT sizing

when sizing fan assist appliances

how far must a chimney terminate above a roof?

3 ft

how far must a chimney be above any obstruction within 10 ft?

2ft

what is the minimum gauge thickness for a vent connector ?

28 GSG

what is the gauge thickness for an incinerator?

20 GSG

what must be used since a single wall vent connector cant pass through a wall or ceiling?

type B

what is the purpose of the 16 GVRs?

they are used to "tailor" the vent sizing table to reflect the installation scenarios

what is the minimum clearance to unprotected combustibles for a single wall vent?

6"

what is the minimum clearance to unprotected combustibles for type B vent?

1"

if the clearance of a single wall vent connector is protected by combustibles, what can the clearance be reduced to?

2"

how much larger should a ventilated thimble be if the vent connector is 6 ft or less long?

4"

how much larger shall a ventilated thimble be if the vent connector is more than 6 ft long?

2 "

how many BTUs is 1 sq in of a power burner?

30 000

how many BTUs is 1 sq in


of an appliance over 1 million MBH

14,000

how many BTUs is 1 sq in


of an appliance under 1 million?

7000

what is the minimum vent height?

5 ft from the highest draft to the rain cap

when can you reduce the size of a draft hooded appliance from


5" to 4" ?

when the vent is 10 ft high

what is the maximum length of a common vent connector?

1.5 ft for every inch of diameter

when shall an outdoor air supply not be required?

when a single water heater with an input of 50 000 btuh or less with no other appliances in the structure.

how many openings must there be for one or more natural draft hood appliances?

2

where must the openings be located for the natural draft hooded appliances?

-no more than 18" from the ground and not less than 6"


-as high as possible to the cieling but no lower than the opening of the lowest draft hood.


where shall an air supply duct be located from a moisture exhaust duct?

3 ft

how high must an air supply inlet be above grade

12" above the outside ground

what type of damper or louvers shall not be used?

-manually operated damper


-manually adjustable louvers

where are BW vents only used?

recessed wall heaters

what is required when a mechanical air supply is used?

the mechanical unit must be interlocked with the appliance it serves

what is the minimum size of opening for air supply?

10 in²

where do type A buildings get their air supply?

Outdoors

where do type B buildings get their air supply?

ALL from outdoors


or


ALL from inside

when a duct exceeds 50 ft, instead of upsizing by 1 size, what must be done?

require a mechanical engineer

the atmospheric pressure inside a building having a category 1 appliance installed must not be allowed to drop more than


....

5 pascals or 0.02" of WC

what is the pressure inside a vent?

-0.03 to -0.1 inch water column

how much does a category 4 appliances terminate above a roof?

18"

what is the maximum length of a comment vent connector?

1.5 ft for each inch of diameter

how is the commen vent height measured for two or more gas fired appliances?

from the highest draft good connection to the rain cap

when must you never use rule of thumb for?

category 1 fan assisted appliances