Maximum gas pressure piped to a residential home

2 PSI

Maximum gas pressure pipe to industrial building

65 PSI natural gas 20 psi propane

In a residential application using propane propane vapor pressure in piping or tubing system between the first and second stage regulator shall not exceed

10 PSIG

For applications using propane a line pressure regulator installed within a residential dwelling shall not be located more than how many feet from the point where the Propane Supply first enters the dwelling

3 feet

Minimum clearance between a pressure regulator and the moisture exhaust duct

3 feet

Can a pressure regulator be bypassed

No

When do you require a positive shut off type line pressure regulator

When the inlet supply pressure to the regulator exceeds 0.5 PSIG

What two things must a line pressure regulator have

Manual shut-off valve installed Upstream of the regulator


Either a line relief device or an overpressure protection device

Where can pressure regulators not be installed

Where it is inaccessible


In a concealed location


where could reasonably expected to be subject to physical or chemical damage

How shall propane Regulators be secured

Firmly secured to The Container valve, or regulator bracket

How many stages shall be utilized on all permanent propane

Minimum 2

How should a regulator that is installed Outdoors or in an unheated area be positioned

So that the Bonnet vent opening discharges vertically downward

A propane regulator installed with a leak limiting device or vent limiting memes shall be installed in what kind of space only

Ventilated

Discharge settings for Relief valves installed in conjunction with line pressure regulators

Not less than 2 times and not more than three times the delivery pressure on systems operating up to 5 PSIG

For natural gas applications when a diaphragm valve or combination control is installed on an appliance and using a gas lighter than air how may it be vented

It may be vented into the appliance combustion chamber adjacent to the continuous pilot

Minimum size of of piping attached to the internal relief or gas over pressure relief valve

At least equal to the nominal pipe size of the vent Outlet of the valve or regulator

The outdoor vent termination of regulators and line relief devices shall be equipped with what to prevent water, insects, or foreign material

A Screen

Clearance of discharge from a regulator relief device from a mechanical air intake

10 ft