Where is an outdoor Air Supply not required when installing a single water heater

When the water heater has an input of 50 MBH and is within an enclosure or structure were no other appliances require an air supply

At what length must you increase the round duct diameter by one size when sizing air supply

20 ft

When an appliance located within an enclosure and a permanent opening is sized and located to allow communication between the enclosure and the rest of the structure the opening provided shell has a free area of not less than

1 inch square per 1000 BTU h

When an opening is made to allow they're into an enclosure from the rest of the structure to provide Air Supply for an appliance where must this opening be located

6 to 18 in above floor level

When an opening is put into a wall for Air Supply from the building as well as the opening near the floor where else do you require an opening

As near the ceiling is practical but in no case lower than the relief opening of the lowest draft controlled device

Where should Air Supply opening terminate near the appliance

Within 1 foot above and within 2 feet horizontally from the burner of the appliance having the largest input

When can a square or rectangular duct be used for Air Supply

When the required free area of the Air Supply opening is 9 in squared or larger

An Air Supply Inlet opening from the outdoors shall be equipped with what

A means to prevent the direct entry of rain and wind and that such mean she'll not reduce required free area of

Minimum height above grade for an air supply Inlet

12 in

Minimum distance from an Air Supply opening to a moisture exhaust

3 feet

At how many BTUs does Supply Air have to come from outside

Over 400,000 BTU

What other consideration must be made when a total input of all appliances exceeds 400,000 BTU

Space containing the appliances must be vented

Minimum chimney size

12 square inches or 4 inch round diameter

When two or more openings are provided into one chimney flue they shall be

At different levels

A chimney must be provided with a

Clean-out opening

Minimum size of a vent

No less than the area of a 3in diameter pipe

Minimum discharge distance of any pool heater to any of building opening

10 feet